Does anybody know which parameters are for the startup-sequence?

I want to reduce the amount of pellet when making a cold startup.
ctctotal
Entusiast!
Inlägg: 112
Blev medlem: tor 19 jan, 2006 09:10
Ort: Oskarshamn

Re: Sekvens Meny

Inlägg av ctctotal »

libi skrev:Does anybody know which parameters are for the startup-sequence?

I want to reduce the amount of pellet when making a cold startup.
Write down the values in the sekvens meny.
Run a cold start-up and take the time on every part of the sequence.
and at the same time check what it does.

I have not found any description in the manual, perhaps check with
a installationcompany.

/Magnus
CTC Total 1983
Thermia Bequem 15D gamla programvaran
3m skorsten
Användarens profilbild
Stugsittaren
Pannrumstomte!
Inlägg: 1185
Blev medlem: tor 22 sep, 2005 14:20
Ort: Norra Sörmland

Re: Sekvens Meny

Inlägg av Stugsittaren »

libi skrev:Does anybody know which parameters are for the startup-sequence?

I want to reduce the amount of pellet when making a cold startup.
Could this adjustment be accessable in a hidden service meny (special password required)?
CTC Ecoflex som värmer ett 60-talshus på 100 m² sedan okt 2006. Ca 3 ton /år. En 5 meters rostfri schiedel-skorsten (120 mm+30 isolering). Tigex 25. Sotar panna + skorsten själv 3 ggr/år. Moderator
ctctotal
Entusiast!
Inlägg: 112
Blev medlem: tor 19 jan, 2006 09:10
Ort: Oskarshamn

Re: Sekvens Meny

Inlägg av ctctotal »

Stugsittaren skrev:
libi skrev:Does anybody know which parameters are for the startup-sequence?

I want to reduce the amount of pellet when making a cold startup.
Could this adjustment be accessable in a hidden service meny (special password required)?
the code is 65, to the sekven meny (0) change the value to 65, after it has stopped blinking, go right and you will find the values
CTC Total 1983
Thermia Bequem 15D gamla programvaran
3m skorsten
ing._med_pellets
Prima virke
Inlägg: 53
Blev medlem: tor 28 jul, 2005 22:46
Ort: Vallentuna

Inlägg av ing._med_pellets »

Hello Libi
I have the following settings in my sequence menu

Cold start, time1, 3 min, displayed as 1K
fan1, 3 min
ignition1, 100 %

time2, 6 min
Start phase 2, 50% , displayed as 2K
time3, 4 min

time4, 0 min
Start phase 4, 0 % displayed as 4K (will not occur when 0%)

time5, 3 min displayed as 5K
time6, 5 min

Start phase6, 20 % displayed as 6K
time7, 8 min displayed as 7K

Hot start
time1V, 60 s displayed as 5V

Stop
time1S, 120 s displayed as STOP

This is how I think it works (possibly not completely correct):
---------------------------------------------------------------------------
Time1 is how long the burner is feeding pellets before starting the fan and ignition starts

Fan1 is how long time the fan and the air heater will be active before entering 2K

Ignition1 is how much of the resulting time of 1K (3 min) the pellets will be fed into the burner. 100% means all the 3 min before entering 2K

Time2 is how long time time after the start of 1K the program will jump into 2K

Start phase2 50% means the feeding through 2K will be 50% of the time

Time3 I do not know for sure. Maybe the time after the start of 2K the program will enter 4K

As soon as the photo cell detects a flame the program will jump into 5K. This could happen any time during 1K through 4K

Time5 is how long time the hotbed will burn with the fan activated but without feeding

Time6 is how much time after entering 5K the fan will start again

Start phase6 is how much of the time the feeding will be activated during 6K

Time7 is how long time after starting 5K the coldstart will finish. The time between 6K and finish is called 7K

Time1V is how long time the burner will feed pellets before finishing a hot start. No fan is active during a hot start

Time1S is how long time after a complete burning cycle the fan will be active

This was a long explanation. I hope i got everything right.

As I thought the burner was waiting to long in 7K waiting for the hotbed to be evenly heated I have shorted down the default value for Time7 to 8 min instead of 10 min. This has worked fine and the burner is now starting faster.

I have also noticed that the cup is often overfilled with pellets during a cold start. Therefore I am thinking of shortening Time1 to 2 min instead of 3 min. Maybe this was an answer for your question Libi? :wink:
Biomatic 20+, hemsnickrat veckoförråd, dragbegränsare.
ctctotal
Entusiast!
Inlägg: 112
Blev medlem: tor 19 jan, 2006 09:10
Ort: Oskarshamn

Inlägg av ctctotal »

Finally a good starting point that has a high potential to be correct
CTC Total 1983
Thermia Bequem 15D gamla programvaran
3m skorsten
Gäst

Inlägg av Gäst »

tack förhand, i´ll try to compare it.


PS: There is no letter like " å " on my keyboard (german layout) :oops:
Senast redigerad av Gäst den tis 14 feb, 2006 07:38, redigerad totalt 1 gånger.
Åland
Gallringsobjekt
Inlägg: 29
Blev medlem: mån 28 nov, 2005 10:10
Ort: Mariehamn Åland

Inlägg av Åland »

Iibi, I'll bring you a swedish keyboard next time I'll go to Zell am Zee! :D
Thermia Biomatic20+
Termomatic ERA
6,5 kbm förråd
Gäst

Inlägg av Gäst »

Yippie! Just through it over the mountains to tyrol! :twisted:

By the way:

Now i think to know, why there are so much pellets in the burners-bowl after a cold startup:

All the sintered material and ash must be transported out of the burner.

If the bowl would be filled only by half, there is always some ash and sintered material inside, which would disturb the burning process (and close the air outlets)
ctctotal
Entusiast!
Inlägg: 112
Blev medlem: tor 19 jan, 2006 09:10
Ort: Oskarshamn

Inlägg av ctctotal »

A new question about the menues
What does it mean the menu with Värme inne och ute 99(40) , -40
is a little unsure about the values?
Is it for the shunt-automatic?
CTC Total 1983
Thermia Bequem 15D gamla programvaran
3m skorsten
Gäst

Inlägg av Gäst »

yes, i think so. you must have a firmware version => v0447.
in my older version v0251 (= year 02 week 51) is no entry like this in the menu.

but i will also depend if you have a biomatic panna or only the solely burner
MF 165
Prima virke
Inlägg: 52
Blev medlem: fre 22 jul, 2005 10:09
Ort: Handen

Inlägg av MF 165 »

ctctotal skrev:A new question about the menues
What does it mean the menu with Värme inne och ute 99(40) , -40
is a little unsure about the values?
Is it for the shunt-automatic?
I asked Thermia about this entry in the menu. Thay answered that it was no functionality, just for test.
CTC 265B
Thermia Bequem 15D
50-säckars "vecko"-förråd, Bulkförråd under utredning.
Snittförbrukning 19kg/dygn